TP FRTEK 40 Fire Resistant Electric Cables

TP FRTEK 40 Fire Resistant Electric Cables

Specification :
TP FRTEK40 is a Fire resistance armoured cable manufactured in accordance to BS 7846-2009.

Fire Performance Test :
BS 7846 Cat.F2, BS 8434, BS EN 50200 + Annex-E

Application :
For the use in Emergency lighting, Essential safety circuits, fire alarm systems, Power supply of various equipments.

Conductor :
Copper conductor (Class 2) to BS EN 60228.

Primary Insulation :
Mica glass fire resistant tape.

Secondary Insulation :
Low smoke zero halogen (LSZH) cross-linkable flame retardant insulation Type EI,5 to BS EN 50363-5.

Inner sheath(Bedding) :
Low smoke zero halogen compound.

Armouring :
Galvanized steel armour round wire.

Sheath :
Thermoplastic Sheath Type LTS 1, having low smoke zero halogen characteristic.

Voltage Rating :
600/1000V.

TP-FRTEK7
TP-FRTEK8
TP FRTEK 40Fire Resistance Cable ensures Circuit Integrity at 950°C for 3 hrs.
TP FRTEK 40Cables are designed to meet the stringent fire survival requirements as perBS 5839when tested toBS 8434 & BS EN 50200.