TP FRTEK 10 Single core Fire Resistant Electric Cables

TP FRTEK 10 Single core Fire Resistant Electric Cables

Specification :
Generally in accordance with BS 7211.

Fire Performance Test :
BS-6387 Categories C.W.Z at 600/1000V.

Application :
Emergengy lighting & Safety circuits where the cable is protected in metal conduit or trunking.

Conductor :
Copper conductor (Class 2) to BS EN 60228.

Primary Insulation :
Mica glass fire resistant tape.

Secondary Insulation :
Low smoke zero halogen (LSZH) cross-linkable flame retardant insulation Type EI,5 to BS EN 50363-5.

Voltage Rating :
600/1000V.

TP-FRTEK1

TP-FRTEK2

In a fire situation conventional PVC FR / FRLS cables used in metal conduits or free air, fail in a short time whereas
TP FRTEK 10maintains circuit Integrity for atleast 3 hrs at 950°C.
TP FRTEK 10is a very good substitute of conventional single corePVC FR/FRLSinsulated cables.