GEMINI POWER CABLES

3 CORE ALUMINUM ARMOURED/UNARMOURED XLPE INSULATED POWER CABLE
1.1, KV Conforming to IS : 7098 (Part-1)
Size sq.mm Min. No. of wires Insulation Thickness (nominal) mm Approx. Overall Diameter DC resistance at 20°C max. ohms/km Current Rating (Amp.)
Unarm Arm In Ground In Air
Wire strip
25 6 0.90 21 23 21 1.20 94 96
35 6 0.90 23 25 23 0.868 113 117
50 6 1.00 25 28 26 0.641 133 142
70 12 1.10 29 32 30 0.443 164 179
95 15 1.10 32 35 32 0.320 196 221
120 15 1.20 35 39 36 0.253 223 257
150 15 1.40 39 42 39 0.206 249 292
185 30 1.60 43 47 44 0.164 282 337
240 30 1.70 48 53 49 0.125 326 199
300 30 1.80 53 58 54 0.100 367 455
400 53 2.00 59 65 60 0.0778 418 530
3.5 CORE ALUMINUM ARMOURED/UNARMOURED XLPE INSULATED POWER CABLES
1.1, KV Conforming to IS : 7098 (Part-1)
Size sq.mm Min. No. of wires Insulation Thickness (nominal) mm Approx. Overall Diameter mm DC resistance at 20°C max. ohms/km Current Rating (Amp.)
Unarm Arm In Ground In Air
Wire Strip
25 6 0.90 22 25 23 1.200 94 96
35 6 0.90 25 27 25 0.868 113 117
50 6 1.00 27 30 28 0.641 133 142
70 12 1.10 31 34 32 0.443 164 179
95 15 1.10 35 38 35 0.320 196 221
120 15 1.20 38 42 39 0.253 223 257
150 15 1.40 42 46 43 0.206 249 292
185 30 1.60 47 51 47 0.164 282 337
240 30 1.70 52 57 53 0.125 326 199
300 30 1.80 57 61 57 0.100 367 455
400 53 2.00 66 71 66 0.0778 418 530
4 CORE ALUMINUM ARMOURED/UNARMOURED XLPE INSULATED POWER CABLES
1.1, KV Conforming to IS : 7098 (Part-1)
Size sq.mm Min. No. of wires Insulation Thickness (nominal) mm Approx. Overall Diameter mm DC resistance at 20°C max. ohms/km Current Rating (Amp.)
Unarm Arm In Ground In Air
wire strip
25.0 6 0.90 23 26 24 1.20 94 96
35.0 6 0.90 26 28 26 0.868 113 117
50.0 6 1.00 29 31 30 0.641 133 142
70.0 12 1.10 33 36 34 0.443 164 179
95.0 15 1.10 36 40 37 0.320 196 221
120.0 15 1.20 41 44 42 0.253 223 257
150.0 15 1.40 45 50 46 0.206 249 292
185.0 30 1.60 50 55 51 0.164 282 337
240.0 30 1.70 56 61 57 0.125 326 199
300.0 30 1.80 63 68 63 0.100 367 455
400.0 53 2.00 71 76 71 0.0778 418 530