Domestic Cables

GEMINI DOMESTIC CABLES

Owing to our consistent efforts for quality and providing the best, we have developed exhaustive range of domestic wires and cables suitable to indian homes and varied conditions. Manufactured with best quality of conductor (electrolytic grade copper, 99.99% pure) and finest grade of indigenously developed PVC compound,

Construction
  • Conductor : Bare annealed copper
  • Insulation : Double layer FR grade PVC insulation with inner layer of neutral PVC and very thin outer layer of colour PVC.
  • Standard : IS 694
  • Sizes : 0.5 sq.mm to 50sq.mm
Application

Tirupati Plastomatics Single core wires can be used in duct, conduit or Aerial wiring for electric power in :

Salient Features
  • Electrolytic Grade copper having 99.99% purity and maximum conductivity to ensure minimum power losses and maximum safety.
  • Bunching of copper in uniform lay & diameter, that makes stripping & crimping of wires easier & minimizes losses.
  • Indigenously developed PVC compound formulated from finest ingredients and produced in-house. High thermal stability & insulation resistance makes it suitable for use in indian environment.
  • Double insulation, with primary insulation from virgin PVC, coated with ultra thin colour layer. This feature enhances safety, and ensures proper colour identification.
SINGLE CORE ELECTRIC WIRE WITH FLEXIBLE COPPER CONDUCTOR
REF : IS : 694/1990 ISI MARKED
Area of Conductor No of Strand/Dia of Strand No./ (mm) Insulation Thickness (nominal) mm Approx. Overall Diameter mm Resistance at 20°C Max. ohm/km Current Rating (Amp.)
0.05 16/0.2 0.70 2.30 39.00 4
0.75 24/0.2 0.70 2.50

26.00

7
1.0 *14/0.3 0.70 2.70 18.10 11
1.5 *22/0.3 0.70 3.00 12.10 14
2.5 *36/0.3 0.80 3.60 7.41 19
4.0 56/0.3 0.80 4.30 4.95 26
6.0 84/0.3 0.80 5.10 3.30 33
10.0 140/0.3 1.00 6.20 1.910 45
16.0 224/0.3 1.00 7.30 1.210 60
25.0 354/0.3 1.20 9.20 0.780 75
35.0 495/0.3 1.20 10.30 0.554 95
50.0 707/0.3 1.40 12.50 0.386 125
SINGLE CORE FR PVC INSULATED STRANDED/SOLID COPPER CONDUCTOR CABLES
REF : IS : 694/1990 ISI MARKED
Area of Conductor No of Strand/Dia of Strand No./ (class 1) No of Strand/Dia of Strand No./ (class 2) Insulation Thickness (mm) nominal Overall Diameter (mm) max Resistance at 20°C Max. ohm/km Current Rating (Amp.)
1.0 1/1.13 7/0.43 0.70 2.80 18.100 5
1.5 1/1.38 7/0.52 0.70 3.10

12.100

14
2.5 1/1.78 7/0.67 0.70 3.80 7.410 18
4.0 1/2.25 7/0.85 0.80 4.30 4.610 24
6.0 1/2.76 7/1.04 0.80 5.30 3.080 31
10.0 1/3.57 7/1.35 1.00 6.60 1.830 43

16.0

7/1.70 1.00 7.90 1.150 57
25.0 7/2.14 1.20 9.50 0.727 74
35.0 7/2.50 1.20 10.80 0.524 90
50.0 19/1.78 1.40 13.20 0.387 123
70.0 19/2.14 1.40 15.00 0.268 177
95.0 19/2.52 1.60 17.50 0.193 205
120.0 37/2.03 1.60 19.00 0.153 235
150.0 37/2.25 1.80 21.00 0.124 280